Authors
Journal
Energy and Buildings
0378-7788
Publisher
Elsevier
Volume
80
Identifiers
DOI: 10.1016/j.enbuild.2014.05.051
Keywords
  • Heat And Moisture Transfer
  • Night Ventilation Rate
  • Indoor Environment
  • Air-Conditioning Load

Abstract

Abstract Night ventilation may improve the indoor air temperature and reduce the cooling load. However, the effects of different night ventilation rates on the indoor air relative humidity, wall inner surface temperature, inner surface moisture flux, sensible heat load, latent heat load and total load are rarely studied in terms of the inner surface moisture transfer. The present paper aims to investigate the effect of different night ventilation rates on the above items in a hot-humid climate in China. The results show the following: when the moisture absorption–desorption process at the wall inner surface is not considered, the air-conditioning load of the night ventilation at 15ACH is approximately 5% lower than that at 5ACH. When the moisture absorption–desorption process is considered, the night ventilation rate has a smaller impact on the indoor air temperature and has a larger impact on the indoor air relative humidity during the night. The night ventilation rate negatively correlates with the sensible heat load and positively correlates with the latent heat load due to the increased amount of moisture that is absorbed or desorbed at the interior wall surface. The total air-conditioning load of Case B.1, which featured a 15ACH night ventilation rate, was approximately 8% higher than that of Case A.1, which featured a 5ACH night ventilation rate.

There are no comments yet on this publication. Be the first to share your thoughts.